Model EC-25 Extended Coverage Area Density Sprinklers
25.2 K-factor


General Description

The Model EC-25 Extended Coverage Upright Sprinklers are Control-Mode Extended Coverage Sprinklers having a nominal K-factor of 25.2. Their use is especially beneficial as a means of decreasing the number of required sprinklers to protect occupancies requiring an area/density application of water.


These sprinklers offer maximum coverage areas of 14 feet by 14 feet (196 sq. ft.) which is almost double that of standard coverage sprinklers used for similar applications.
The EC-25 has successfully undergone full scale fire testing at FM for use under obstructed ceiling conditions for area/density design applications. This testing has demonstrated that the Model EC-25 at its extended coverage spacings can be installed using all other standard coverage sprinkler criteria. As such, they are acceptable for all currently recognized area/density applications.

IMPORTANT
Always refer to Technical Data Sheet TFP700 for the INSTALLER WARNING that provides cautions with respect to handling and installation of sprinkler systems and comĀ­ponents. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.











Technical Data Sheet TFP 213